Chapter 5 Function parameter
108
The function code is used to set analog quantity and its corresponding setting when the
analog input voltage is less than the set Minimum Input.
Units digit, tens digit and hundreds digit the function code respectively correspond to
the analog input AI1, AI2, panel potentiometer. If 0 is selected, when the analog input is less
than the Minimum Input, the setting corresponding to the analog amount is the setting of
minimum input of the function code curve (F1.13, F1.17, F1.21).
If 1 is selected, when the analog input is less than the minimum input, the setting
corresponding to the analog amount is 0.0%.
F1.26
Minimum pulse input
frequency
0.00kHz to F1.28
0.00kHz
F1.27
Minimum pulse input
frequency setting
-100.0% to +100.0%
0.0%
F1.28
Maximum pulse input
frequency
F1.26 to +100.00kHz
50.00kHz
F1.29
Maximum pulse input
frequency setting
-100.0% to +100.0%
100.0%
This group function code is used to set the relationship between DI5 pulse frequency
and its corresponding setting.
Pulse frequency can be inputted into the inverter only through DI5 channel. The
application on this group of functions is similar to curve 1, please refer to the description of
curve 1.
F1.30
DI filter time
0.000s to 1.000s
0
.
010s
Set software filter time for DI terminals status. For the application that input terminals
are vulnerable to interference and cause the accidental operation, you can increase this
parameter so as to enhance the anti-interference ability. However, the increase of filter time
will cause DI terminal slow response.
F1.31
AI
1 filter time
0.00s to 10.00s
0.10s
F1.32
AI2 filter time
0.00s to 10.00s
0.10s
F1.33
Filtering time of panel
potentiometer
0.00s to 10.00s
0.10s
F1.34
Filter time of pulse
input
0.00s to 10.00s
0.00s
F1.35
DI terminal valid
mode selection 1
Units
digit
DI1
terminal active
status setting
00000
High level active
0
Low level active
1
Tens digit
DI2 terminal
active status
setting (0 to 1, as
above)
Hundreds
digit
DI3 terminal
active status