4-18 Description of Diagnostic Messages F… and E… ECODRIVE03-SGP-03VRS
DOK-ECODR3-SGP-03VRS**-WA01-EN-P
F406 Phase switching without ready signal
The SERCOS master attempted a phase switch without waiting for the
drive controller’s ready signal.
Cause:
Error in the SERCOS master module of the control system.
Remedy:
Consult the control system manufacturer.
See also the functional description: "SERCOS interface error"
F407 Error during initialization of master communication
An error occurred during the initialization and check of the master
communication interface between drive processor and field bus
processor.
Note: This error cannot be cleared and the drive remains in phase 2.
It is possible to parameterize the axis and carry out a firmware
update with DOLFI. The axis, however, cannot be moved!
Cause:
The error F407 Error during initialization of master communication is
entered, if
• there has no master communication card been plugged in.
• the wrong master communication card has been plugged in.
• the master communication firmware is not running (timeout).
• an error of the master communication card has occurred.
Remedy:
• Plug in the right master communication card
• Replace the firmware
F408 Fatal error of the interface card
The fieldbus interface has detected a fatal error.
Cause:
1. The watchdog of the interface card has been triggered.
1. A non-permitted memory access follows.
Recovery:
Switch unit off and on and if error still pending, replace hardware.
F434 Emergency-Stop
Pressing the emergency stop switch (E-Stop) has caused the drive to
perform the emergency stop function that was selected in the P-0-0119,
Best possible deceleration parameter. Setting bit 15 of S-0-0011, Class
1 diagnostics causes an error message to be issued to the controller.