ECODRIVE03-SGP-03VRS Description of Diagnostic Messages F… and E… 4-29
DOK-ECODR3-SGP-03VRS**-WA01-EN-P
E226 Undervoltage in power section
If bit 5 of the P-0-0118, Power off on error parameter has been set, an
undervoltage condition will be handled as a nonfatal warning. The drive
issues this warning if the drive enabling signal is present and the DC bus
voltage message disappears.
Cause:
Power supply unit is switched off or mains failure occurs while the drive
enabling signal is set.
Remedy:
Switch off the drive enabling signal before you switch off the power supply
unit.
E247 Interpolation velocity = 0
The drive-internal position command value interpolator is active if
• the "drive-internal interpolation" mode
• the "relative drive-internal interpolation" mode
• drive-controlled homing
• jog
• drive halt
• process block mode
is active.
The E247 warning is issued if the employed velocity specification is 0.
Possible velocity specifications are:
• S-0-0259, Positioning velocity
• S-0-0041, Homing velocity
• S-0-0091, Bipolar velocity limit value
• P-0-4030, Jog velocity
• P-0-4007, Process block velocity
Note: Warning E247 is suppressed if S-0-0259, Positioning
Velocity is cyclically configured.
See also the functional description: "Operating Mode: Drive Internal
Interpolation"
E248 Interpolation acceleration = 0
Cause:
The drive internal position command interpolator (profile generator) is
active. It has been given the acceleration = 0. Without acceleration, it can
never reach a given speed.