5-12 Description of Diagnostic Messages B…; C…, D… and A ECODRIVE03-SGP-03VRS
DOK-ECODR3-SGP-03VRS**-WA01-EN-P
Remedy:
Check and set the relevant parameters correctly as follows:
• S-0-0160, Acceleration data scaling type
• S-0-0161, Acceleration data scaling factor
• S-0-0162, Acceleration data scaling exponent
• S-0-0116, Resolution of motor feedback
• S-0-0121, Input revolutions of load gear
• S-0-0122, Output revolutions of load gear
• S-0-0123, Feed constant
• P-0-0074, Interface feedback 1
• S-0-0277, Position feedback 1 type parameter
See also the functional description "S-0-0128, C200 Communication
phase 4 transition check".
C216 Torque/force data scaling error
Cause:
The display format of the torque/force data can be set using torque/force
scaling parameters. The factor for converting torque data from drive-
controlled format to display format (or vice-versa) is outside the allowable
area.
Remedy:
Check and set the relevant parameters correctly as follows:
• S-0-0086, Torque/force data scaling type
• S-0-0093, Torque/force data scaling factor
• S-0-0094, Torque/force data scaling exponent
• S-0-0110, Amplifier peak current
• S-0-0111, Motor current at standstill
See also the functional description "S-0-0128, C200 Communication
phase 4 transition check".
C217 Feedback1 data reading error
All MKD und MHD motors have a data memory in the feedback unit. From
there, settings for the encoder are read.
Cause:
During reading of the values from the feedback, an error has occurred.
Remedy:
Check feedback cable.
Change motor.
See also the functional description "S-0-0128, C200 Communication
Phase 4 Transition Check".