ECODRIVE03-SGP-03VRS Description of Diagnostic Messages B…; C…, D… and A 5-7
DOK-ECODR3-SGP-03VRS**-WA01-EN-P
C113 Relation TNcyc (S-0-0001) to TScyc (S-0-0002) error
Cause:
The value of S-0-0001, NC Cycle time (TNcyc) can only be equal to or
be a multiple of S-0-0002, SERCOS Cycle time (Tscyc). Here this is not
the case.
Remedy:
S-0-0001, NC Cycle time (Tncyc) and S-0-0002, SERCOS Cycle time
(Tscyc) must be corrected. These parameters are determined by the
manufacturer of the control system and are specified by the SERCOS
interface.
See also the functional description: "Configuration of the telegram send
and receive times"
C114 T4 > TScyc (S-0-0002) - T4min (S-0-0005)
Cause:
The maximum permissible value for S-0-0007, Feedback acquisition
starting time (T4) is
S-0-0002, SERCOS Cycle time (Tscyc) -
S-0-0005, Minimum feedback acquisition time(T4min)
The value for S-0-0007, Feedback acquisition starting time (T4) is
incorrect.
Remedy:
Correct S-0-0007, Feedback acquisition starting time (T4). These
parameters are determined by the manufacturer of the control system and
are specified by the SERCOS interface.
See also the functional description: "Configuration of the telegram send
and receive times"
C115 T2 too small
Cause:
The value set for S-0-0089, MDT Transmit starting time (T2) is
incorrect. The drive cannot work with this value.
Remedy:
Correct S-0-0089, MDT Transmit starting time (T2).
These parameters are determined by the manufacturer of the control
system, and are specified by the SERCOS interface.
See also the functional description: "Configuration of the telegram send
and receive times"
C118 Order of MDT configuration wrong