5-8 Description of Diagnostic Messages B; C, D and A ECODRIVE03-SGP-03VRS
DOK-ECODR3-SGP-03VRS**-WA01-EN-P
The chronological order of processing the cyclical MDT data in the drive is
the same order in which the configurated ident numbers (IDN) are placed
in the parameter S-0-0024, Config. list of the master-data-telegram.
For the usage of the multiplex mode in the MDT, there are the parameters
S-0-0360, MDT Data container A
S-0-0368, Addressing for data container A
S-0-0362, List index, MDT data container A
If more than one of these parameters is configured in the MDT, their
correct order is checked in the command S-0-0127, C100
Communication phase 3 transition check. The following rules must be
obeyed:
S-0-0368, Addressing for data container A must be configured as
the first of the 3 parameters above.
S-0-0360, MDT Data container A must be configured as the last of
the 3 parameters above.
If this is not the case, the drive generates the command error C118 Order
of MDT configuration wrong.
C200 Communication phase 4 transition check
Meaning:
The command S-0-0128, C200 Communication phase 4 transition
check has been activated.
See also the functional description "S-0-0128, C200 Communication
phase 4 transition check".
C201 Invalid parameter(s) (->S-0-0022)
Cause:
Parameters which will be necessary to operate the drive in
communications phase 4 are invalid. The invalid parameters can be seen
in S-0-0022, IDN list of invalid op. data for comm. ph. 3.
Remedy:
The parameters of S-0-0022, IDN list of invalid op. data for comm. ph.
3 must be rewritten so they are correct.
See also the functional description "S-0-0128, C200 Communication
phase 4 transition check".
C202 Parameter limit error (->S-0-0022)
Cause:
Parameters which are necessary to operate the drive in communications
phase 4 are outside of their minimum or maximum input values, or the
entered value cant be processed (for bit bars). The incorrect parameters
are listed in S-0-0022, IDN list of invalid op. data for comm. ph. 3.
Remedy:
The parameters of S-0-0022, IDN list of invalid op. data for comm. ph.
3 must be rewritten with correct values.
See also the functional description "S-0-0128, C200 Communication
phase 4 transition check".