Publication 2094-UM001A-EN-P — September 2006
178 Specifications and Dimensions
Use class CC, J, L, or R fuses, with current rating as indicated in the
table below. The following fuse examples and Allen-Bradley circuit
breakers are recommended for use with integrated axis modules
(2094-xCxx-Mxx-S) when the Line Interface Module (LIM) is not used.
Fuse Specifications
IMPORTANT
Line Interface Modules (2094-ALxxS, -BLxxS, and -XL75S-Cx)
provide branch circuit protection to the IAM. Follow all
applicable NEC and local codes.
Catalog Number
V ac Input Power Control Input Power DC Common Bus Fuse
Bussmann
Fuse
Allen-Bradley
Circuit Breaker
(1)
Bussmann
Fuse
Allen-Bradley
Circuit Breaker
(1)
Bussmann
Fuse
Ferraz
Shawmut Fuse
2094-AC05-MP5-S
KTK-R-20 (20 A) 1492-CB3H300 140M-F8E-C16
FNQ-R-10 (10 A)
1492-CB2H060
N/A A50P20-1
2094-AC05-M01-S
2094-AC09-M02-S KTK-R-30 (30 A) 1492-CB3H400 140M-F8E-C20 FWH-35B A50P35-4
2094-AC16-M03-S LPJ-45SP (45 A) N/A 140U-H6C3-C50
1492-SP2D200
FWH-60B A50P60-4
2094-AC32-M05-S LPJ-80SP (80 A) N/A 140U-H6C3-C90 FWH-125B A50P125-4
2094-BC01-MP5-S
KTK-R-20 (20 A) 1492-CB3H300 140M-F8E-C32
1492-CB2H060
N/A A100P20-1
2094-BC01-M01-S
2094-BC02-M02-S KTK-R-30 (30 A) 1492-CB3H400 140M-F8E-C45 FWJ-40A A100P40-1
2094-BC04-M03-S LPJ-45SP (45 A)
N/A
140U-H6C3-C50 FWJ-70A A100P70-1
2094-BC07-M05-S LPJ-80SP (80 A) 140U-H6C3-C90 FWJ-125A A100P125-1
(1)
When using Bulletin 1492 circuit protection devices, the maximum short circuit current available from the source is limited to 5000 A.
ATTENTION
Bulletin 1492 and 140M circuit breakers should not be used on
the output of an ac drive as an isolating disconnect switch or
motor overload device. These devices are designed to operate
on sine wave voltage and the drive’s PWM waveform does not
allow it to operate properly. As a result, damage to the device
will occur.