4-26 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Motor OL Current
Set to the maximum allowable current. The drive fault on an F7 Motor Over load if
the value of this parameter is exceeded by 150% for 60 seconds.
Parameter Number 133
Related Parameter
155, 158, 161, 189, 190, 198,
214, 218
Access Rule GET/SET
Data Type UINT
Group Basic Program
Units 0.1 A
Minimum Value 0.0
Maximum Value Drive rated amps x 2
Default Value Based on Drive Rating
Minimum Freq
Sets the lowest frequency the drive will output continuously.
Parameter Number 134
Related Parameter
101, 102, 113, 135, 185, 186,
187, 210, 212
Access Rule GET/SET
Data Type UINT
Group Basic Program
Units 0.1 Hz
Minimum Value 0.0
Maximum Value 400
Default Value 0.0
Maximum Freq
Sets the Highest frequency the drive will output continuously.
Parameter Number 135
Related Parameter
101, 102, 113, 134, 135, 178,
185, 186, 187, 211, 213
Access Rule GET/SET
Data Type UINT
Group Basic Program
Units 0.1 Hz
Minimum Value 0.0
Maximum Value 400
Default Value 60.0
Start Source
Sets the control scheme used to start the Bulletin 284G ArmorStart.
2 = 2-wire
3 = 2-wire Level Sensitive
4 = 2-wire High Speed
5 = RS485 (DSI) Port
Parameter Number 136
Related Parameters 112 and 137
Access Rule GET/SET
Data Type UINT
Group Basic Program
Units —
Minimum Value 0
Maximum Value 5
Default Value 5
Stop drive before changing this parameter.
Stop drive before changing this parameter.