4-46 Bulletin 284G Programmable Parameters for Sensorless Vector Controllers
Figure 4.6
Anlg In 0…10V Lo
Sets the analog input level that corresponds to parameter 134 (Minimum Freq) if a
0…10V input is used by parameter 138 (Speed Reference)
Parameter Number 210
Related Parameter 121, 134, 138, 222
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1%
Minimum Value 0.0%
Maximum Value 100.0%
Default Value 0.0%
Stop drive before changing this parameter.
Anlg In 0…10V HI
Sets the analog input level that corresponds to parameter 135 (Maximum Freq) if a
0…10V input is used by parameter 138 (Speed Reference). Analog inversion can be
accomplished by setting this value smaller than parameter 210 (Anlg In 0…10V Lo).
Parameter Number 211
Related Parameter 121, 135, 138, 222, 223
Access Rule GET/SET
Data Type UINT
Group Advanced Program Group
Units 0.1%
Minimum Value 0.0%
Maximum Value 100.0%
Default Value 0.0%
Anlg In4…20MA LO
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number 212
Anlg In4…20 mA HI
This parameter is not available for use with the ArmorStart Distributed Motor
Controller.
Parameter Number 213
0
Parameter 135
[Maximum Freq]
Parameter 134
[Minimum Freq]
Parameter 210
[Anlg In 0-10V Lo]
Parameter 211
[Anlg In 0-10V Hi]
0
Speed Reference
Stop drive before changing this parameter.