EasyManua.ls Logo

Rosemount 8712C - Page 56

Rosemount 8712C
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model 8712C/U/H Magnetic Flowmeter Transmitters
5-6
TABLE 5-3. Flowtube
Troubleshooting
Test A–Flowtube Coil
Step 1 Step 2 Step 3
Disconnect power from the transmitter
by removing the fuse. Disconnect wires
1and2fromthetransmitter.
Measure the resistance across wires 1
and 2 going to the flowtube, using the
lowest ohms scale. The reading should
be between 2 and 18 V.
A reading outside this range indicates
that the coils or cables may be open
or shorted.
Test B Coil Shield to Coil
Step 1 Step 2 Step 3
Disconnect power from the transmitter
by removing the fuse. Disconnect wires
1, 2, and ground from the transmitter.
Measure the resistance from the coil
shield (ground) to wires 1 and 2 using
the highest scale. Both readings should
be overrange.
Any reading on the scale indicates that
the coils are shorted to the housing.
Test C Electrode Shield to Electrode (See Note Below)
Step 1 Step 2 Step 3
Disconnect power from the transmitter
by removing the fuse. Disconnect wires
17, 18, and 19 from the transmitter. Test
with process in the flowtube (either flow
or no flow).
Measuretheresistancefromwire17to
18and17to19.Thisreadingwill
change as you hold the leads on the
wires, so use the initial reading.
These readings should both be between
1kV and 3 MV and close to each other.
A reading near 68kV or 0V indicates a
possible shorted electrode. A stable
reading indicates a shorted electrode.
A high reading indicates a possible
coated electrode, non-conductive
process, or electrode not in contact
with process.
Test D Positive to Negative Electrode (See Note Below)
Step 1 Step 2 Step 3
Disconnect power from the transmitter
by removing the fuse. Disconnect wires
18, and 19 from the transmitter.Testwith
process in the flowtube (either flow or
no flow).
Measure the resistance between wires
18 and 19. This reading should be in the
range between 100 kV and 2MV.
An overrange reading indicates a coated
electrode, non-conductive process,
or electrode not in contact with the
process.

Table of Contents

Related product manuals