Chapter 5 Configuring T H E P M 1 3 0 P L U S
Configuring R E C O R D E R S
PM130 PLUS Powermeter Series 101
Configuring the Event Recorder
To configure the Event log file:
1. Double click on the Event Log file partition with the left mouse
button.
2. Select a desired file type for your file.
3. Select the maximum number of records you want to be recorded in
the file.
4. Click OK, then send your new setup to the meter or save to the
device database.
By default, the Event recorder stores all events related to configuration
changes, resets, and device diagnostics.
Configuring the Data Recorder
Conventional Data Log Files
The Data recorder is programmable for recording up to 9 data parameters
per record in each of the conventional data log files. The list of parameters
to be recorded to a data log is configurable individually for each file.
To create a new data log file or re-configure an existing file:
1. Double click on the file partition with the left mouse button.
2. Select a partition type for your file.