Chapter 5 Configuring T H E P M 1 3 0 P L U S
General M E T E R S E T U P
PM130 PLUS Powermeter Series 87
Figure 5-11: General Setup Dialog Box Pulse/Event Counters
You can preset a counter to a required value or clear it without affecting
the counter setup.
To preset or clear a counter:
1. Click the Online button on the PAS toolbar before accessing the setup
dialog box.
2. Type in the required value into the Counter Value field.
3. Click Send.
Configuring Alarm/Control Setpoints
The PM130 PLUS has an embedded logical controller that can perform
different actions in response to user-defined internal and external events.
Unlike a PLC, the meter uses a simplified programming technique based
on setpoints that allows the user to define a logical expression based on
measured analog and digital values that produce a required action.
The meter provides 16 control setpoints with programmable operate and
release delays. Each setpoint evaluates a logical expression with one
trigger argument. Whenever an expression is evaluated as “true”, the
setpoint performs a programmable action that can send a command to the
output relay, or increment a counter.
The logical controller provides very fast response to events. The scan time
for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400
Hz).

Table of Contents

Other manuals for Satec PM130E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satec PM130E and is the answer not in the manual?

Satec PM130E Specifications

General IconGeneral
BrandSatec
ModelPM130E
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals