EasyManua.ls Logo

Schweitzer Engineering SEL-387-0 - Page 218

Schweitzer Engineering SEL-387-0
556 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SET.6 of 35 SEL-387-0, -5, -6 Relay Settings Sheets
Group Settings (SET Command)
SEL-387-0, -5, -6 Relay Instruction Manual Date Code 20170601
Date________________
Phase Inst. O/C Level 2 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P22P =
50P22 Torque Control (SEL
OGIC control equation)
50P22TC =
Phase Inst. O/C Level 3 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P23P =
Phase Inst. O/C Level 4 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P24P =
Phase Inv.-Time O/C PU
(OFF, 0.5–16.0 A secondary) (5 A)
(OFF, 0.1–3.2 A secondary) (1 A)
51P2P =
Phase Inv.-Time O/C Curve (U1–U5, C1–C5)
51P2C =
Phase Inv.-Time O/C Time-Dial (US 0.5–15.0, IEC 0.05–1.00)
51P2TD =
Phase Inv.-Time O/C EM Reset (Y, N)
51P2RS =
51P2 Torque Control (SEL
OGIC control equation)
51P2TC =
Winding 2 Negative-Sequence O/C Elements
NOTE: All negative-sequence element pickup settings are in terms of 3I
2
.
Neg.-Seq. Def.-Time O/C Level 1 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50Q21P =
Neg.-Seq. Level 1 O/C Delay (0.5–16000 cycles)
50Q21D =
50Q21 Torque Control (SEL
OGIC control equation)
50Q21TC =
Neg.-Seq. Inst. O/C Level 2 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50Q22P =
50Q22 Torque Control (SEL
OGIC control equation)
50Q22TC =
Neg.-Seq. Inv.-Time O/C PU
(OFF, 0.5–16.0 A secondary) (5 A)
(OFF, 0.1–3.2 A secondary) (1 A)
51Q2P =
Neg.-Seq. Inv.-Time O/C Curve (U1–U5, C1–C5)
51Q2C =

Table of Contents