1.8
SEL-387-0, -5, -6 Relay Instruction Manual Date Code 20170601
Specifications
Specifications
Compliance
Designed and manufactured under an ISO 9001 certified quality
management system
UL Listed to U.S. and Canadian safety standards (File E212775;
NRGU, NRGU7)
CE Mark
RCM Mark
General
AC Current Inputs
5 A nominal: 15 A continuous, 500 A for 1 s,
linear to 100 A symmetrical, 1250 A
for 1 cycle
Burden: 0.27 VA at 5 A
2.51 VA at 15 A
1 A nominal: 3 A continuous, 100 A for 1 s,
linear to 20 A symmetrical, 250 A for
1 cycle
Burden: 0.13 VA at 1 A
1.31 VA at 3 A
Power Supply
125/250 Vdc or Vac
Range: 85–350 Vdc or 85–264 Vac
Burden: <25 W
Interruption: 45 ms at 125 Vdc
Ripple: 100%
48/125 Vdc or 125 Vac
Range: 38–200 Vdc or 85–140 Vac
Burden: <25 W
Interruption: 160 ms at 125 Vdc
Ripple: 100%
24/48 Vdc
Range: 18–60 Vdc polarity dependent
Burden: <25 W
Interruption: 110 ms at 48 Vdc
Ripple: 100%
Note: Interruption and Ripple per IEC 60255-11:1979.
Output Contacts
Standard:
Make: 30 A
Carry: 6 A continuous carry at 70°C
4 A continuous carry at 85°C
1 s Rating: 50 A
MOV Protection: 270 Vac/360 Vdc; 130 J
Pickup Time: <5 ms
Dropout Time: <5 ms, typical
Breaking Capacity (10,000 Operations):
24 V 0.75 A L/R = 40 ms
48 V 0.50 A L/R = 40 ms
125 V 0.30 A L/R = 40 ms
250 V 0.20 A L/R = 40 ms
Cyclic Capacity (2.5 Cycles/Second):
24 V 0.75 A L/R = 40 ms
48 V 0.50 A L/R = 40 ms
125 V 0.30 A L/R = 40 ms
250 V 0.20 A L/R = 40 ms
High-Current Interrupting Option:
Make: 30 A
Carry: 6 A continuous carry at 70°C
4 A continuous carry at 85°C
1 s Rating: 50 A
MOV Protection: 330 Vdc; 130 J
Pickup Time: <5 ms
Dropout Time: <8 ms, typical
Breaking Capacity (10,000 Operations):
24 V 10 A L/R = 40 ms
48 V 10 A L/R = 40 ms
125 V 10 A L/R = 40 ms
250 V 10 A L/R = 20 ms
Cyclic Capacity (4 Cycles in 1 Second Followed by 2 Minutes
Idle for Thermal Dissipation):
24 V 10 A L/R = 40 ms
48 V 10 A L/R = 40 ms
125 V 10 A L/R = 40 ms
250 V 10 A L/R = 20 ms
Note: Do not use high current interrupting output contacts to switch
ac control signals. These outputs are polarity dependent.
Note: Make per IEEE C37.90-1989; Breaking and Cyclic Capacity
per IEC 60255-23:1994.
Optoisolated Inputs
Contact inputs have a fixed, 1/4-cycle debounce time
250 Vdc: Pickup 200–300 Vdc; Dropout 150 Vdc
220 Vdc: Pickup 176–264 Vdc; Dropout 132 Vdc
125 Vdc: Pickup 105–150 Vdc; Dropout 75 Vdc
110 Vdc: Pickup 88–132 Vdc; Dropout 66 Vdc
48 Vdc: Pickup 38.4–60 Vdc; Dropout 28.8 Vdc
24 Vdc: Pickup 15.0–30 Vdc
Note: 24, 48, and 125 Vdc optoisolated inputs draw approx. 4 mA
of current; 110 Vdc inputs draw approx. 8 mA of current; and 220
and 250 Vdc inputs draw approx. 5 mA of current. All current
ratings are at nominal input voltage.
Frequency and Rotation
System Frequency: 50 or 60 Hz
Phase Rotation: ABC or ACB
Communications Ports
EIA-232: 1 front and 2 rear
EIA-485: 1 rear, 2100 Vdc isolation
Baud Rate: 300–19200 bps
Operating Temperature
–40 to +85C (–40 to +185F)
Time-Code Input
Relay accepts demodulated IRIG-B time-code input at Port 1 or 2.
Relay is time synchronized to within ±5 ms of time source input.