SET.10
of 35
SEL-387-0, -5, -6 Relay Settings Sheets
Group Settings (SET Command)
SEL-387-0, -5, -6 Relay Instruction Manual Date Code 20170601
Date________________
51N3 Torque Control (SELOGIC control equation)
51N3TC =
Winding 3 Demand Metering
Demand Ammeter Time Constant (OFF, 5–255 min) DATC3 =
Phase Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
PDEM3P =
Neg.-Seq. Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
QDEM3P =
Residual Demand Ammeter Threshold
(0.5–16.0 A secondary) (5 A)
(0.1–3.2 A secondary) (1 A)
NDEM3P =
Winding 4 O/C Elements
Winding 4 Phase O/C Elements
Phase Def.-Time O/C Level 1 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P41P =
Phase Level 1 O/C Delay (0–16000 cycles)
50P41D =
50P41 Torque Control (SEL
OGIC control equation)
50P41TC =
Phase Inst. O/C Level 2 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P42P =
50P42 Torque Control SEL
OGIC control equation)
50P42TC =
Phase Inst. O/C Level 3 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P43P =
Phase Inst. O/C Level 4 PU
(OFF, 0.25–100.00 A secondary) (5 A)
(OFF, 0.05–20.00 A secondary) (1 A)
50P44P =
Phase Inv.-Time O/C PU
(OFF, 0.5–16.0 A secondary) (5 A)
(OFF, 0.1–3.2 A secondary) (1 A)
51P4P =
Phase Inv.-Time O/C Curve (U1–U5, C1–C5)
51P4C =

Table of Contents