7.15
Date Code 20170601 Instruction Manual SEL-387-0, -5, -6 Relay
Serial Port Communications and Commands
SEL ASCII Protocol Details
The following display indicates successful access to Level B:
=>BAC <Enter>
Password: ? @@@@@
XFMR 1 Date: 11/11/96 Time: 14:04:51.251
STATION A
Breaker Level
==>
The relay pulses the ALARM contact closed for one second after any Level B
access attempt unless an alarm condition already exists.
BRE (Breaker Report)
Access Levels 1, B, 2
Use the BREAKER command to display a report of breaker operation
information. The breaker report provides trip counter and trip current
information for up to four breakers. The summary of the operations provides
valuable breaker diagnostic information at a glance. An example breaker
report follows. Refer to Section 5: Metering and Monitoring for further
information. If the Analog Input Label settings (IAW1, etc.) have been
renamed, these will appear in the report as set.
=>>BRE <Enter>
XFMR 1 Date: 06/19/97 Time: 21:04:30.973
STATION A
BREAKER 1
Int Trips= 4 IAW1= 0.01 IBW1= 0.01 ICW1= 0.02 kA(pri)
Ext Trips= 15 IAW1= 1.04 IBW1= 0.50 ICW1= 0.16 kA(pri)
Percent Wear: POLE1= 0 POLE2= 0 POLE3= 0
BREAKER 2
Int Trips= 3 IAW2= 59.31 IBW2= 0.09 ICW2= 0.08 kA(pri)
Ext Trips= 14 IAW2= 160.91 IBW2= 1.70 ICW2= 0.33 kA(pri)
Percent Wear: POLE1= 88 POLE2= 0 POLE3= 0
BREAKER 3
Int Trips= 11 IAW3= 316.47 IBW3= 0.33 ICW3= 0.46 kA(pri)
Ext Trips= 6 IAW3= 6.32 IBW3= 3.03 ICW3= 0.24 kA(pri)
Percent Wear: POLE1= 100 POLE2= 0 POLE3= 0
BREAKER 4
Int Trips= 0 IAW4= 0.00 IBW4= 0.00 ICW4= 0.00 kA(pri)
Ext Trips= 0 IAW4= 0.00 IBW4= 0.00 ICW4= 0.00 kA(pri)
Percent Wear: POLE1= 0 POLE2= 0 POLE3= 0
LAST BREAKER MONITOR RESET FOR Bkr1: 06/12/97 16:02:07.407
Bkr2: 06/12/97 16:02:07.533
Bkr3: 06/12/97 16:02:07.651
Bkr4: 06/12/97 16:02:07.758
=>>
BRE R n (Breaker Reset)
Access Levels B, 2
The BRE R n command resets the trip counter, trip current data and contact
wear percentages for Breaker n. Issue BRE R A to reset all Breaker Monitors
at one time. Use the BRE command to verify resetting of the data.