SEL-387-0, -5, -6 Relay Instruction Manual Date Code 20170601
SEL-387 Relay Command Summary
MET H Generate harmonic spectrum report for all input currents, showing first to fifteenth harmonic levels in secondary
amperes.
MET P k Display peak demand metering data, in primary amperes. Enter number k to scroll metering k times on screen.
MET RD n Reset demand metering values (n = 1, 2, 3, 4, A).
MET RP n Reset peak demand metering values (n = 1, 2, 3, 4, A).
MET SEC k Display metering data (magnitude and phase angle), in secondary amperes. Enter number k to scroll metering k
times on screen.
MET T Report temperature values of up to 24 RTD inputs (SEL-387-5 and SEL-387-6 Relays only).
QUI Quit. Returns to Access Level 0. Returns front-panel LEDs to the default targets.
SER d1 Show rows in the Sequential Events Recorder (SER) event report for date d1.
SER d1 d2 Show rows in the Sequential Events Recorder (SER) event report from date d1 to d2. Entry of dates is dependent
on the Date Format setting DATE_F (= MDY or YMD).
SER m n Show rows m through n in the Sequential Events Recorder (SER) event report.
SER n Show the latest n rows in the Sequential Events Recorder (SER) event report.
SER C Clear the Sequential Events Recorder (SER) event reports from memory.
SHO n Show relay group n settings. Shows active group if n is not specified.
SHO G Show relay global settings.
SHO P Show port settings and identification of port to which user is connected.
SHO P n Show port settings for port n (n =1, 2, 3, 4).
SHO R Show Sequential Events Recorder (SER) settings.
STA Show relay self-test status.
STA C Clear relay status report from memory and reboot the relay.
TAR n k Show Relay Word row n status (n = 0 through 41). Enter number k to scroll Relay Word row n status k times on
screen.
Append F to display targets on the front panel, second row of LEDs.
T
AR R Return front-panel LED targets to regular operation and reset the tripping front-panel targets.
All commands that begin TFE apply to the SEL-387-5 and SEL-387-6 Relays
TFE Displays cumulative and individual through-fault event data. The twenty (20) most recent individual events are
displayed.
TFE n Displays cumulative and individual through-fault event data. The n most recent individual events are displayed,
where n = 1 to 1200.
TFE A Displays cumulative and individual through-fault event data. All the most recent individual events are displayed,
up to 1200.
TFE C Clears/resets cumulative and individual through-fault event data.
TFE P Preloads cumulative through-fault event data.
TFE R Clears/resets cumulative and individual through-fault event data.
Access Level 1
Commands
The Access Level 1 commands primarily allow the user to look at information
(e.g., settings, metering, etc.), but not to change it. The screen prompt is: =>

Table of Contents