10.7
Date Code 20170601 Instruction Manual SEL-387-0, -5, -6 Relay
Testing and Troubleshooting
Acceptance Testing
Press RETURN to continue
DATC3 = 15 PDEM3P = 7.00 QDEM3P = 1.00 NDEM3P = 1.00
TMWDG = 1 VWDG = 230 XTYPE = 3 TRTYPE = Y
THwr = 65 NCS = 1
MCS11 = 100.0
DTMP = 15 TRDE =0
NTHM = 2 AMB = THM1 OIL1 = THM2
TOT1 = 100 TOT2 = 100 HST1 = 200 HST2 = 200
FAAL1 = 50.00 FAAL2 = 50.00 RLOLL = 50.00 TLOLL = 50.00
CSEP1 = 15
ILIFE = 180000 EDFTC = Y
TDURD = 9.000 CFD = 60.000
TR1 =50P11T + 51P1T + 51Q1T + OC1 + LB3
TR2 =51P2T + 51Q2T + OC2
TR3 =50P31 + 51P3T + OC3
TR4 =87R + 87U
TR5 =0
ULTR1 =!50P13
ULTR2 =!50P23
Press RETURN to continue
ULTR3 =!50P33
ULTR4 =!(50P13 + 50P23 + 50P33)
ULTR5 =0
52A1 =IN101
52A2 =IN102
52A3 =IN103
52A4 =0
CL1 =CC1 + LB4 + /IN104
CL2 =CC2 + /IN105
CL3 =CC3 + /IN106
CL4 =0
ULCL1 =TRIP1 + TRIP4
ULCL2 =TRIP2 + TRIP4
ULCL3 =TRIP3 + TRIP4
ULCL4 =0
ER =/50P11 + /51P1 + /51Q1 + /51P2 + /51Q2 + /51P3
OUT101 =TRIP1
OUT102 =TRIP2
OUT103 =TRIP3
OUT104 =TRIP4
Press RETURN to continue
OUT105 =CLS1
OUT106 =CLS2
OUT107 =CLS3
OUT201 =0
OUT202 =0
OUT203 =0
OUT204 =0
OUT205 =0
OUT206 =0
OUT207 =0
OUT208 =0
OUT209 =0
OUT210 =0
OUT211 =0
OUT212 =0
SCEUSE 47.1
GR1CHK 9FAE
Outputs
Step 1. Purpose: Verify that contact outputs operate when you execute
the PULSE command.
Method:
a. Isolate all circuitry connected to the output contacts.
b. Set the target LEDs to display the contact outputs by
typing TAR F OUT101 <Enter>. The front-panel
LEDs should now follow Row 41 of the Relay Word
where OUT101 is listed.