Date Code 20170601 Instruction Manual SEL-387-0, -5, -6 Relay
Testing and Troubleshooting
Acceptance Testing
SLP2 Restrained Differential Threshold
Step 1. Purpose: Verify the differential characteristic settings and set
winding compensation.
Method:
a. Execute the SHO TAP1 <Enter> command via the
relay front panel or serial port and verify the (TAPn)
settings, the Restraint Slope 1 Percentage (SLP1)
setting, the Restraint Slope 2 Percentage (SLP2)
setting, and the restraint current slope 1 limit (IRS1)
setting.
b. Execute the SET W1CTC <Enter> command and set
the WnCTC settings for the two windings to be used to
the same value.
c. Save the settings.
Step 2. Purpose: Display the appropriate Relay Word bit on the front-
panel LEDs.
Method: Execute the TARGET command (i.e., TAR F 87R
<Enter>). The SEL-387 now displays the state of several
differential elements in the second row of the front-panel
LEDs. The 87R bit is the right-most LED.
Step 3. Purpose: Select a test point on the percentage differential curve
in Figure 10.6.
Method: Decide where you want to cross the differential
characteristic by picking a restraint value IRT that is a vertical
line on the graph. Since this test is for the SLP2 threshold,
select a point above the IRS1 setting.
IRT > IRS1
The value of IOP that corresponds to the selected IRT is as
follows:
Equation 10.9
Both IRT and IOP are in multiples of tap.
Step 4. Purpose: Calculate the expected current for Winding 1 and
Winding 2 at the restrained differential element SLP2 threshold
for the test point selected above.
Method: Calculate the Winding 1 current for the test using the
following formula:
Equation 10.10
Calculate the Winding 2 current for the test using the following formula:
. Equation 10.11
The A connection compensation constant is based on
Table 10.4. Since the windings have the same WnCTC setting,
the A constant will be the same for both windings. The A
IOP
SLP2
100
-------------- IRT IRS1
SLP1 SLP2–
100
----------------------------------


• +• =
IAW1 IRT 1
SLP2
200
--------------+


RS1
SLP1 SLP2–
200
----------------------------------


• +•


TAP1 A• • =
IAW2 IRT 1
SLP2
200
--------------–


IRS1
SLP1 SLP2–
200
----------------------------------


• –•


TAP2 A• • =