D.14
SEL-387-0, -5, -6 Relay Instruction Manual Date Code 20170601
Configuration, Fast Meter, and Fast Operate Commands
Message Definitions
The ALIAS settings are ignored for the SNS command (i.e., if ALIAS1 =
OUT101 CL_BKR_1, SNS includes “OUT101”, not the custom label). Refer
to Settings in Section 6: Setting the Relay.
SNS message for the SEL-387-5 is:
<STX>"xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","yyyy"<CR>
"xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","xxxx","yyyy"<CR>
"xxxx","xxxx","xxxx",<CR><ETX>
where:
xxxx = a string from the settings in SER (SER1, SER2, SER3,
and SER4).
yyyy = the 4-byte ASCII representation of the checksum.