EasyManua.ls Logo

Schweitzer Engineering SEL-387-0 - Page 506

Schweitzer Engineering SEL-387-0
556 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
G.10
SEL-387-0, -5, -6 Relay Instruction Manual Date Code 20170601
Distributed Network Protocol
DNP3 Documentation
30,32 22,23 IRW magnitude and angle for Wdg. 2.
30,32 24,25 IA magnitude and angle for Wdg. 3.
30,32 26,27 IB magnitude and angle for Wdg. 3.
30,32 28,29 IC magnitude and angle for Wdg. 3.
30,32 30,31 3I1 magnitude and angle for Wdg. 3.
30,32 32,33 3I2 magnitude and angle for Wdg. 3.
30,32 34,35 IRW magnitude and angle for Wdg. 3.
30,32 36,37 IA magnitude and angle for Wdg. 4.
30,32 38,39 IB magnitude and angle for Wdg. 4.
30,32 40,41 IC magnitude and angle for Wdg. 4.
30,32 42,43 3I1 magnitude and angle for Wdg. 4.
30,32 44,45 3I2 magnitude and angle for Wdg. 4.
30,32 46,47 IRW magnitude and angle for Wdg. 4.
30,32 48 IOP1 Operate Current.
30,32 49 IOP2 Operate Current.
30,32 50 IOP3 Operate Current.
30,32 51 IRT1 Restraint Current.
30,32 52 IRT2 Restraint Current.
30,32 53 IRT3 Restraint Current.
30,32 54 I1F2 Second-Harmonic Current.
30,32 55 I2F2 Second-Harmonic Current.
30,32 56 I3F2 Second-Harmonic Current.
30,32 57 I1F5 Fifth-Harmonic Current.
30,32 58 I2F5 Fifth-Harmonic Current.
30,32 59 I3F5 Fifth-Harmonic Current.
30,32 60 VDC.
30,32 61–65 Demand A, B, C, 3I2, and IR magnitudes for Wdg. 1.
30,32 66–70 Demand A, B, C, 312, and IR magnitudes for Wdg. 2.
30,32 71–75 Demand A, B, C, 312, and IR magnitudes for Wdg. 3.
30,32 76–80 Demand A, B, C, 312, and IR magnitudes for Wdg. 4.
30,32 81 Peak demand IA mag. for Wdg.1.
30 82–84 Peak demand IA time in DNP format for Wdg.1.
30,32 85 Peak demand IB mag. for Wdg.1.
30 86–88 Peak demand IB time in DNP format for Wdg.1.
30,32 89 Peak demand IC mag. for Wdg.1.
30 90–92 Peak demand IC time in DNP format for Wdg.1.
30,32 93 Peak demand 312 mag. for Wdg.1.
30 94–96 Peak demand 312 time in DNP format for Wdg.1.
30,32 97 Peak demand IR mag. for Wdg.1.
30 98–100 Peak demand IR time in DNP format for Wdg.1.
Table G.5 SEL-387 Relay-Wye/Delta DNP Data Map (Sheet 3 of 4)
DNP
Object Type
Index Description