7
Operation
Binary controller
Operating Instructions – MOVIMOT
®
advanced
122
7.2.4 Configuration 3: Enable, external fault, setpoint changeover
Fixed setpoint processing mode: Mechanical setting elements
(cannot be changed)
Behavior of the drive unit Digital input "DRIVE"
LED
DI01 DI02 DI03 DI04
Enable Ex-
ternal
fault
Poten-
tiometer
f2
Reset
The drive unit stops with deceleration setpoint t1.
1)
FCB01 Output stage inhibit is activated afterwards.
0 1 x x Lights up
yellow
The drive unit is running in positive direction of rotation
(clockwise rotation) with speed setpointf1.
2)
The acceleration setpoint t1 is active.
1)
1 1 0 x Illuminated
in green
The drive unit is running in positive direction of rotation
(clockwise rotation) with speed setpointf2.
The acceleration setpoint t1 is active.
1)
1 1 1 x Illuminated
in green
The drive unit is in state "External terminal fault". 1 0 x x Flashing
red
The fault state has been reset. 0 1 0 1 Lights up
yellow
1) If potentiometer t1 is deactivated using the parameter settings, the acceleration setpoint 1/ deceleration setpoint 1 of the fixed set-
point processing will be activated.
2) If DIP switch S2/2 (Analog setpoint selection) is set to "ON", the speed setpoint of analog input AI1 is used instead of speed setpoint
f1.
0 = No voltage 1 = 24V x = Any