12
Functional safety
Safety conditions
Operating Instructions – MOVIMOT
®
advanced
286
12.3.2 Requirements on the installation
The wiring technology used must comply with the standard EN60204-1.
The STO control cables must be routed according to EMC guidelines and as fol-
lows:
Inside an electrical installation space: Single conductors can be routed.
Outside a closed installation space: Shielded cables must be routed perman-
ently (fixed) and protected against external damage, or equivalent measures
must be taken.
Adhere to the regulations in force for the application.
The sinking and sourcing cables from the external safety device to the axis
must be routed right next to each other with a cable length of ≤100m.
The sinking and sourcing cables from the external safety device to the axis
must have the same cable length. A difference in length ≤ 3% of the two cables
is permitted.
Using suitable measures. the user must ensure that STO control cables are
routed separately from the power lines of the drive. This does not apply to
cables approved by SEW‑EURODRIVE specifically for this application case.
The STO function does not detect short circuits or interference voltage in the sup-
ply line. For this reason, one of the following 2 requirements must always be met:
No parasitic voltages can occur in the STO control cables
The external safety controller can detect a crossfault from an external potential
to the STO control lines.
Observe without fail the values specified for safety components when designing
the safety circuits.
The STO signal (F_STO_P1, F_STO_P2, and F_STO_M) must not be used for
feedback.
For safety controller/safety relays, you must only use grounded voltage sources
with protective electrical separation (PELV) in accordance with EN 61131-2 and
EN60204-1.
If several voltage sources are used, each voltage source must be connected to a
PE system.
When planning the installation, observe the technical data of the devices.
Do not use the port 24V_OUT of the device for safety-related applications. This
voltage is only permitted to supply the M12 plug connector X5504 when the STO
jumper is plugged in.
When the STO control cables are routed to Terminal X9 in the electronics cover,
the cable ends must be covered with conductor end sleeves and the cables must
be fixed close to the terminal X9 using cable ties. Other low-voltage signals can be
bundled together with the STO signals.
To use the drive unit in safety-related applications, remove the jumpers labeled
with "Caution, remove jumper for safety operation" from the STO terminal X9. No
labeled jumpers are available for those designs where the STO connection is per-
formed using plug connectors. The installed jumper is relevant to the function.
25891936/EN – 05/2020

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SEW-Eurodrive MOVIMOT advanced DRN DBC Series and is the answer not in the manual?

SEW-Eurodrive MOVIMOT advanced DRN DBC Series Specifications

General IconGeneral
BrandSEW-Eurodrive
ModelMOVIMOT advanced DRN DBC Series
CategoryDC Drives
LanguageEnglish

Related product manuals