Operating Instructions – Electronic Motor DRC.-..-SNI
151
10
Error table
Service
Error 50 Internal voltage supply too
low
Output stage
inhibit / locked
• Hardware defective → Contact SEW Service.
Error 52 Machine control error Output stage
inhibit / locked
• Operation without encoder a speed that is too low → Increase
speed
• Load too high in controlled operation → Reduce load on the drive
Reset error by switching the unit off or via error reset function.
Consult SEW Service if the error recurs.
Error 53 CPU error Output stage
inhibit / locked
Reset error by switching the unit off or via error reset function.
Consult SEW Service if the error recurs.
Error 77 IPOS error Output stage
inhibit / locked
Faulty IPOS program (e.g. invalid command)
→ Correct program
Reset error by switching the unit off or via error reset function.
Error 89 Only in conjunction with
DRC electronic motor:
Overtemperature in brake
Output stage
inhibit / locked
Brake coil not sufficient to dissipate the regenerative energy.
→ Use braking resistor
Wrong size of braking resistor selected.
→ Use larger braking resistor
Error 94 Checksum error Output stage
inhibit / locked
NV memory defective.
→ Contact SEW Service
Error 97 Parameter transmission
error
Output stage
inhibit / locked
Error during data transmission
→ Repeat copying process
Set the delivery status and re-parameterize the unit.
Error 116 MOVI-PLC
®
timeout Emergency
stop/waiting
Timeout in communication with higher-level controller
Error 119 Safety error Output stage
inhibit / locked
Safety hardware faulty
→ Contact SEW Service
Error 123 Positioning interruption
error
Stop / waiting Target monitoring when interrupted positioning process is resumed.
Target would be overrun.
→ Perform positioning process without interruption until it is complete.
Error code Description Switch-off
response
Cause/solution