EXAMPLE
Add a Marker command (SPC) signal to the information list.
[sc_add_SPC_signal_1ph, 1, en_US]
Figure 7-25
Adding Marker Command (SPC) Signal to Information List
Set up the following CFC. Connect the SPC signal as input, and the signal
>Reset all counters
as
output.
[sc_CFC_60C_1ph, 1, en_US]
Figure 7-26 Function Chart (CFC): Activating the Binary Input Signal
Send a single-point control command from the control center to the SPC signal to activate the signal
>Reset all counters
. Then the counters are reset.
Settings
Addr.
Parameter C Setting Options Default Setting
MP selection
_:13501:100 MP selection:Consistency
failure
no MP configured
no Sensor configured
no MP config-
ured
7.5.3.3
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase
1010 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017