Addr. Parameter C Setting Options Default Setting
_:5131:106 Device combin.:Address
of device 5
1 to 65534 105
_:5131:107 Device combin.:Address
of device 6
1 to 65534 106
_:5131:101 Device combin.:Local
device is device
1 to 6 1
_:5131:122 Device combin.:Lowest
appearing bit rate
•
64 kBit/s
•
128 kBit/s
•
512 kBit/s
•
2048 kBit/s
64 kBit/s
_:5131:125 Device combin.:Number
of devices
2 to 6 6
Prot. interf.1
_:5161:1 Prot. interf.1:Mode
•
off
•
on
on
_:5161:105 Prot. interf.1:Max. error
rate per hour
0.000 % to 100.000 % 1.000 %
_:5161:106 Prot. interf.1:Max. error
rate per min
0.000 % to 100.000 % 1.000 %
_:5161:107 Prot. interf.1:Disturb-
ance alarm after
0.05 s to 2.00 s 0.10 s
_:5161:108 Prot. interf.1:Transm.
fail. alarm after
0.0 s to 6.0 s 6.0 s
_:5161:109 Prot. interf.1:Delay time
threshold
0.1 ms to 30.0 ms 30.0 ms
_:5161:110 Prot. interf.1:Difference
Tx and Rx time
0.000 ms to 3.000 ms 0.100 ms
_:5161:113 Prot. interf.1:PPS
synchronization
•
telegr. and PPS
•
telegr. or PPS
•
PPS sync. off
PPS sync. off
Information List
No.
Information Data Class
(Type)
Type
Channel 1
_:307 Prot.interface:Health ENS O
_:304 Prot.interface:Channel Live SPS O
Device combin.
_:5131:52 Device combin.:Behavior ENS O
_:5131:53 Device combin.:Health ENS O
_:5131:301 Device combin.:Status of topo. recog. ENS O
_:5131:302 Device combin.:Topology is ENS O
_:5131:303 Device combin.:Devices form ENS O
_:5131:304 Device combin.:Number of detect. dev. INS O
_:5131:305 Device combin.:Fct. logoff device 1 SPS O
_:5131:306 Device combin.:Fct. logoff device 2 SPS O
_:5131:307 Device combin.:Fct. logoff device 3 SPS O
_:5131:309 Device combin.:Fct. logoff device 4 SPS O
_:5131:310 Device combin.:Fct. logoff device 5 SPS O
_:5131:311 Device combin.:Fct. logoff device 6 SPS O
3.5.3.12
System Functions
3.5 Protection Communication
SIPROTEC 5, Overcurrent Protection, Manual 143