Output signal:
Retrip T1
The output signal
Retrip T1
must be routed to a binary output.
If only one control circuit is available for the local circuit breaker, the output signal must be routed to the
binary output to which the general circuit breaker trip command (command
Position
) is routed.
If a second control circuit is present, the
Retrip T1
output signal can be routed to the associated binary
output.
Output signal:
Trip T2
In order to trip the adjacent circuit breakers, the backup tripping (indication
Trip T2
) must be routed to a
binary output and if necessary, to an interface (intertripping to the opposite end). Thus, the circuit breaker on
the opposite end can be tripped without delay.
Settings
Addr. Parameter C Setting Options Default Setting
Restrike prt.#
_:1 Restrike prt.#:Mode
•
off
•
on
•
test
off
_:101 Restrike prt.#:Plausibility
via 50BF fct.
•
no
•
yes
no
_:102 Restrike prt.#:Plaus. via
open/trip cmd
•
no
•
yes
no
_:103 Restrike prt.#:Plaus. via
binary input
•
no
•
yes
no
_:106 Restrike prt.#:Retrip after
T1
•
no
•
start T2 after T1
•
parallel start T2, T1
start T2 after T1
_:104 Restrike prt.#:Monitoring
duration
1.00 s to 600.00 s 200.00 s
_:105 Restrike prt.#:Position
recognition delay
0.00 s to 60.00 s 0.02 s
_:3 Restrike prt.#:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.250 A
5 A @ 50 Irated 0.15 A to 175.00 A 1.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.250 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 1.250 A
_:7 Restrike prt.#:Dropout
delay
0.00 s to 60.00 s 0.05 s
_:107 Restrike prt.#:Delay T1
for 3-pole retrip
0.00 s to 60.00 s 0.00 s
_:108 Restrike prt.#:Delay T2
for 3-pole trip
0.05 s to 60.00 s 0.15 s
_:109 Restrike prt.#:Minimum
operate time
0.00 s to 60.00 s 0.15 s