Settings
Addr. Parameter C Setting Options Default Setting
Stage 1
_:391:1 Stage 1:Mode
off
on
test
off
_:391:2 Stage 1:Operate & flt.rec.
blocked
no
yes
no
_:391:9 Stage 1:Measured value
VA measured
VB measured
VC measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:391:8 Stage 1:Method of measure-
ment
fundamental comp.
RMS value
fundamental
comp.
_:391:3 Stage 1:Threshold 0.300 V to 340.000 V 110.000 V
_:391:4 Stage 1:Dropout ratio 0.90 to 0.99 0.95
_:391:6 Stage 1:Operate delay 0.00 s to 60.00 s 3.00 s
Stage 2
_:392:1 Stage 2:Mode
off
on
test
off
_:392:2 Stage 2:Operate & flt.rec.
blocked
no
yes
no
_:392:9 Stage 2:Measured value
VA measured
VB measured
VC measured
VAB measured
VBC measured
VCA measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:392:8 Stage 2:Method of measure-
ment
fundamental comp.
RMS value
fundamental
comp.
_:392:3 Stage 2:Threshold 0.300 V to 340.000 V 130.000 V
_:392:4 Stage 2:Dropout ratio 0.90 to 0.99 0.95
_:392:6 Stage 2:Operate delay 0.00 s to 60.00 s 0.50 s
Information List
No.
Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Stage 1
_:391:81 Stage 1:>Block stage SPS I
6.27.5
6.27.6
Protection and Automation Functions
6.27 Overvoltage Protection with Any Voltage
SIPROTEC 5, Overcurrent Protection, Manual 725
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals