the device switches to another channel (etc.). Once switched to a current channel, the system automatically
switches back to the voltage channel if a voltage channel is valid again.
Parameter Value Description
inactive
If the channels of the measuring point are not to be considered for deter-
mining the sampling frequency, please select the setting value inactive.
active
If you have set the parameter Tracking = active, the measuring point
will be included when determining the sampling frequency.
Note: If the parameter Tracking = active, the determined sampling
frequency applies to all functions in the device not using fixed sampling
rates.
Parameter: Magnitude correction
Default setting (_:3811:103) Magnitude correction = 1.000
When using the Magnitude correction parameter, the magnitude (magnitude correction) is adjusted for
the voltage input. This allows you to correct the tolerances of the primary current transformer phase-selec-
tively. The magnitude correction may be required for highly precise measurements. Use a comparison meas-
urement to determine the setting value (for example, with a high-precision measuring-voltage transformer). If
a primary correction is not necessary, retain the default setting.
i
i
NOTE
The Magnitude correction parameter has nothing to do with the internal adjustment of the input
circuit.
Settings
General Information
Addr.
Parameter C Setting Options Default Setting
General
_:2311:101 General:Phase sequence
ABC
ACB
ABC
Measuring Point I-3ph
Addr.
Parameter C Setting Options Default Setting
General
_:8881:115 CT 3-phase:CT connec-
tion
not assigned
3-phase + IN
3-phase
3-phase + IN-separate
3-phase, 2 primary CT
2
3ph,2prim.CT + IN-sep
2ph, 2p. CT + IN-sep
3-phase + IN
_:8881:127 CT 3-phase:Tracking
inactive
active
active
_:8881:130 CT 3-phase:Measuring-
point ID
0 to 100 0
CT phases
_:8881:101 CT 3-phase:Rated
primary current
1.0 A to 100 000.0 A 1000.0 A
6.1.8
Protection and Automation Functions
6.1 Power-System Data
312 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017