Addr. Parameter C Setting Options Default Setting
_:12601:110 3I0> cos/sinφ1:Blk. after
fault extinction
no
yes
yes
_:12601:108 3I0> cos/sinφ1:Direc-
tional mode
forward
reverse
forward
_:12601:109 3I0> cos/sinφ1:Dir.
measuring method
cos φ
sin φ
cos φ
_:12601:107 3I0> cos/sinφ1:φ correc-
tion
-45 ° to 45 ° 0 °
_:12601:102 3I0> cos/
sinφ1:Min.polar.3I0> for
dir.det.
1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.150 A
_:12601:105 3I0> cos/sinφ1:α1 reduc-
tion dir. area
1 ° to 15 ° 2 °
_:12601:106 3I0> cos/sinφ1:α2 reduc-
tion dir. area
1 ° to 15 ° 2 °
_:12601:101 3I0> cos/sinφ1:3I0>
threshold value
1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.250 A
_:12601:103 3I0> cos/sinφ1:V0>
threshold value
0.300 V to 200.000 V 30.000 V
_:12601:104 3I0> cos/sinφ1:Dir.
determination delay
0.00 s to 60.00 s 0.10 s
_:12601:6 3I0> cos/sinφ1:Operate
delay
0.00 s to 60.00 s 2.00 s
Information List
No.
Information Data Class
(Type)
Type
3I0> cos/sinφ1
_:12601:81 3I0> cos/sinφ1:>Block stage SPS I
_:12601:501 3I0> cos/sinφ1:>Block delay & op. SPS I
_:12601:54 3I0> cos/sinφ1:Inactive SPS O
_:12601:52 3I0> cos/sinφ1:Behavior ENS O
_:12601:53 3I0> cos/sinφ1:Health ENS O
_:12601:60 3I0> cos/sinφ1:Inrush blocks operate ACT O
_:12601:302 3I0> cos/sinφ1:Ground fault ACD O
_:12601:55 3I0> cos/sinφ1:Pickup ACD O
_:12601:56 3I0> cos/sinφ1:Operate delay expired ACT O
_:12601:57 3I0> cos/sinφ1:Operate ACT O
6.15.4.4
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual 577
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals