Indication Type Group
Warning
Explanation
VI-3ph: Mess.Volt.Fail detected:
(_:300) Failure
SPS CFC
Measuring-voltage failure detected:
Check the exterior wiring.
Blocking: Appropriate functions are
either blocked definitely or the blocking
can be set individually.
Defect Severity 2
Faults of defect severity 2 are fatal device faults that lead to an immediate restart of the device (reset).
This occurs when the device data is corrupted (for example, RAM memory), if a restart prevents restoration of
data consistency. The device goes briefly out of operation, a failure is avoided.
Life contact Is terminated during the restart
Red error LED Is activated during the restart
i
i
NOTE
If the fault of defect severity 2 has not be been removed after 3 unsuccessful restarts (reset), the fault is
automatically assigned to defect severity 3. The device will automatically turn to the fallback mode.
Log
For every device error with a subsequent restart (reset), only the restart can be detected in the operational log.
The actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detec-
tion and before the restart. These indications are recorded with a real-time stamp and are thus available for
later analyses. The device-diagnosis log contains expanded fault descriptions. There you also receive recom-
mendations of corresponding corrective measures for each detected device error.
You can find further information on handling the logs in chapter 3.
Overview of Errors
Number
Device-Diagnosis Log
826 Processor error on the base module:
If the fault occurs numerous times, contact the Customer Support Center.
830 FPGA hardware error on the base module:
Contact the Customer Support Center.
834 Memory error (short term):
Reset initiated.
3823 Program run error:
If the fault occurs numerous times, contact the Customer Support Center.
826 CPU overload:
If the fault occurs numerous times, contact the Customer Support Center.
Miscellaneous Internal firmware error:
If the fault occurs numerous times, contact the Customer Support Center.
Defect Severity 3
Faults of defect severity 3 are fatal device faults that lead to device immediately going into the fallback mode.
The signal
(_:301) Device status
goes to the Alarm state. The Warning state is not supported for this
signal.
9.8.3
9.8.4
Supervision Functions
9.8 Error Responses and Corrective Measures
SIPROTEC 5, Overcurrent Protection, Manual 1301
C53000-G5040-C017-8, Edition 07.2017