Superv.Grp.#
_:52 Superv.Grp.#:Behavior ENS O
_:55 Superv.Grp.#:Sig. volt. disturbed SPS O
Voltage-Transformer Circuit Breaker
Overview of Functions
The Voltage-transformer circuit breaker function detects the tripping of the voltage-transformer circuit
breaker due to short circuits in the voltage-transformer secondary circuits.
The Voltage-transformer circuit breaker function works independently of Measuring-voltage failure detec-
tion and should be used – if possible – in parallel to it.
The tripping of the voltage-transformer circuit breaker has an impact on the quality of the recorded measured-
value data (see chapter 3.3 Processing Quality Attributes).
The following protection function is automatically blocked in cases of the tripping of the voltage-transformer
circuit breaker:
•
Directional negative-sequence protection
For the following functions the reaction (block/not block) can be set within the function in cases of a tripping
of the voltage-transformer circuit breaker:
•
Directional time-overcurrent protection, phases
•
Directional time-overcurrent protection, ground
•
Directional sensitive ground-fault detection
•
Overvoltage protection with negative-sequence voltage
•
Overvoltage protection with zero-sequence voltage/residual voltage
•
Undervoltage protection with 3-phase voltage
•
Undervoltage protection with positive-sequence voltage