Settings
Addr. Parameter C Setting Options Default Setting
Inverse-T #
_:1 Inverse-T #:Mode
off
on
test
off
_:2 Inverse-T #:Operate &
flt.rec. blocked
no
yes
no
_:10 Inverse-T #:Blk. by
meas.-volt. failure
no
yes
yes
_:9 Inverse-T #:Measured
value
phase-to-ground
phase-to-phase
phase-to-phase
_:8 Inverse-T #:Method of
measurement
fundamental comp.
RMS value
fundamental
comp.
_:101 Inverse-T #:Pickup mode
1 out of 3
3 out of 3
1 out of 3
_:102 Inverse-T #:Pickup delay
no
yes
no
_:3 Inverse-T #:Threshold 0.300 V to 175.000 V 80.000 V
_:109 Inverse-T #:Pickup factor 0.80 to 1.00 0.90
_:103 Inverse-T #:Charact.
constant k
0.00 to 300.00 1.00
_:104 Inverse-T #:Charact.
constant α
0.010 to 5.000 1.000
_:105 Inverse-T #:Charact.
constant c
0.000 to 5.000 0.000
_:106 Inverse-T #:Time dial 0.05 to 15.00 1.00
_:107 Inverse-T #:Additional
time delay
0.00 s to 60.00 s 0.00 s
_:108 Inverse-T #:Reset time 0.00 s to 60.00 s 0.00 s
Information List
No.
Information Data Class
(Type)
Type
Inverse-T #
_:81 Inverse-T #:>Block stage SPS I
_:54 Inverse-T #:Inactive SPS O
_:52 Inverse-T #:Behavior ENS O
_:53 Inverse-T #:Health ENS O
_:55 Inverse-T #:Pickup ACD O
_:300 Inverse-T #:Pickup loop AB SPS O
_:301 Inverse-T #:Pickup loop BC SPS O
_:302 Inverse-T #:Pickup loop CA SPS O
_:56 Inverse-T #:Operate delay expired ACT O
_:57 Inverse-T #:Operate ACT O
6.29.4.3
6.29.4.4
Protection and Automation Functions
6.29 Undervoltage Protection with 3-Phase Voltage
SIPROTEC 5, Overcurrent Protection, Manual 749
C53000-G5040-C017-8, Edition 07.2017