Text Structure and Reference Number for Settings and Indications
Each parameter and each indication has a unique reference number within every SIPROTEC 5 device. The
reference number gives you a clear reference, for example, between an indication entry in the buffer of the
device and the corresponding description in the manual. You can find the reference numbers in this docu-
ment, for example, in the application and setting notes, in the logic diagrams, and in the parameter and infor-
mation lists.
In order to form unique texts and reference numbers, each function group, function, function block/stage, and
indication or parameter has a text and a number. This means that structured overall texts and numbers are
created.
The structure of the texts and the reference numbers follow the hierarchy already shown in Figure 2-1.
Function group:Function:Stage/Function Block:Indication
Function group:Function:Stage/Function Block:Parameter
The colon serves as a structure element to separate the hierarchy levels. Depending on the functionality, not
all hierarchy levels are always available. Function Group and Stage/Function block are optional. Since the func-
tion groups, functions as well as tripping stages/function blocks of the same type can be created multiple
times, a so-called instance number is added to these elements.
EXAMPLE
The structure of the text and reference number is shown in the protection-function group Line as an example
of the parameter Threshold value and the indication Pickup of the 2nd definite time-overcurrent protec-
tion stage of the function Overcurrent protection, phases (see Figure 2-9). Only one function and one func-
tion group exist in the device. The representation of the stage is simplified.
[lostuumz-180311-01.tif, 1, en_US]
Figure 2-9 Stage of the Overcurrent Protection Function, Phases (without Representation of Stage
Control)
The following table shows the texts and numbers of the hierarchy elements concerned:
Name Number of the
Type
Instance Number
Protection function group Line 2 1
Function Overcurrent 3ph 20 1
Stage Definite time-overcurrent
protection
66 2
Settings Threshold value 3
Indication Pickup 55
The instance numbers arise as follows:
Function group: Line 1
1 instance, because only one Line function group exists in the device
Function: Overcurrent 3ph 1
1 instance, because only one Overcurrent 3ph function exists in the Line function group
2.4
Basic Structure of the Function
2.4 Text Structure and Reference Number for Settings and Indications
SIPROTEC 5, Overcurrent Protection, Manual 57