Addr. Parameter C Setting Options Default Setting
_:16351:137 90V V.contr.gc:V< Time
delay
0 s to 20 s 0 s
_:16351:138 90V V.contr.gc:I>
Blocking
•
off
•
on
on
_:16351:139 90V V.contr.gc:I>
Threshold
10 % to 500 % 150 %
_:16351:140 90V V.contr.gc:I> Time
delay
0 s to 20 s 0 s
_:16351:141 90V V.contr.gc:I<
Blocking
•
off
•
on
off
_:16351:142 90V V.contr.gc:I<
Threshold
3 % to 100 % 10 %
_:16351:143 90V V.contr.gc:I< Time
delay
0 s to 20 s 10 s
Information List
Two-Winding Transformer
No. Information Data Class
(Type)
Type
General
_:2311:52 General:Behavior ENS O
_:2311:53 General:Health ENS O
Tap changer
_:13981:500 Tap changer:>Acquisition blocking SPS I
_:13981:501 Tap changer:>Enable SPS I
_:13981:53 Tap changer:Health ENS O
_:13981:301 Tap changer:End higher pos.reached SPS O
_:13981:302 Tap changer:End lower pos.reached SPS O
_:13981:308 Tap changer:Position BALANCED
SCORECARD
C
_:13981:305 Tap changer:Higher command SPS O
_:13981:306 Tap changer:Lower command SPS O
_:13981:307 Tap changer:Command active SPS O
_:13981:309 Tap changer:Motor sup. time expired SPS O
_:13981:310 Tap changer:Trigger motor prot. sw. SPS O
_:13981:311 Tap changer:Position failure SPS O
_:13981:312 Tap changer:Op.ct. INS O
_:13981:319 Tap changer:Reset failure SPC C
90V V.contr.2w
_:14011:81 90V V.contr.2w:>Block SPS I
_:14011:85 90V V.contr.2w:>Reset min./max. SPS I
_:14011:53 90V V.contr.2w:Health ENS O
_:14011:54 90V V.contr.2w:Inactive SPS O
_:14011:52 90V V.contr.2w:Behavior ENS O
_:14011:301 90V V.contr.2w:End Higher pos. Auto SPS O
_:14011:302 90V V.contr.2w:End Lower pos. Auto SPS O
8.9.6
Control Functions
8.9 Voltage Controller
SIPROTEC 5, Overcurrent Protection, Manual 1231
C53000-G5040-C017-8, Edition 07.2017