Addr. Parameter C Setting Options Default Setting
_:13501:81 MP selection:MP selec-
tion
Setting options depend on
configuration
General
_:2311:101 General:Automatic
compensation
•
no
•
yes
no
_:2311:100 General:Normalization
with Ic
•
no
•
yes
no
_:2311:102 General:Thresh. defec-
tive C-elem.
1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.150 A
_:2311:104 General:De-energ.time
w/o comp.
0.00 s to 60.00 s 2.00 s
Information List
No. Information Data Class
(Type)
Type
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
General
_:2311:500 General:>Compensate SPS I
_:2311:501 General:>Reset comp. val. SPS I
_:2311:502 General:>Reset all counters SPS I
_:2311:302 General:Alg. not compensated SPS O
_:2311:303 General:Compens. succeeded SPS O
_:2311:304 General:Comp. via BI blk.(Ic<) SPS O
_:2311:305 General:I>-stage(cmp) blk.(Ic<) SPS O
_:2311:306 General:No auto. comp. config. SPS O
_:2311:307 General:C defect counted SPS O
_:2311:308 General:Unknown dir. phase A SPS O
_:2311:309 General:Unknown dir. phase B SPS O
_:2311:310 General:Unknown dir. phase C SPS O
_:2311:311 General:Df. G1 A INS O
_:2311:312 General:Df. G1 B INS O
_:2311:313 General:Df. G1 C INS O
_:2311:314 General:Df. G2 A INS O
_:2311:315 General:Df. G2 B INS O
_:2311:316 General:Df. G2 C INS O
_:2311:300 General:Iunbl.cp CMV O
_:2311:301 General:Iunbl. CMV O
_:2311:323 General:Cp.vect. CMV O
7.5.3.4
Capacitor Bank Protection
7.5 Current-Unbalance Protection for Capacitors, 1-Phase
SIPROTEC 5, Overcurrent Protection, Manual 1011