EasyManua.ls Logo

Siemens 7SJ82 - Circuit-Breaker Restrike Protection; Overview of Function; Structure of the Function; Function Description

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Circuit-Breaker Restrike Protection
Overview of Function
The Circuit-breaker restrike protection function:
Monitors the circuit breaker against restriking, for example, caused by an overvoltage over the circuit-
breaker poles after switching off a capacitor bank
Generates a backup operate signal in case of a circuit-breaker restriking
Structure of the Function
The Circuit-breaker restrike protection function is used in the Circuit-breaker function group. A maximum
of 2 functions can operate simultaneously within the function group.
[lo_strrestrike_2014-03-05.vsd, 2, en_US]
Figure 6-257 Structure/Embedding of the Function
The function logic is grouped into the parts shown in Figure 6-258. In the following chapter, these logic parts
are described in detail.
[lo_respro-210113-01.vsd, 1, en_US]
Figure 6-258 Logic Overview of the Function
Function Description
Plausibility Release
The function Circuit-breaker restrike protection issues a trip command to a superordinated circuit breaker,
usually the infeed circuit breaker of a busbar. Overfunction of this protection can cause extreme problems for
the whole application.
The logic of plausibility release strongly reduces the risk of a false start of the function by adding an extra
release criteria for a function start.
Each criterion can be switched on or off individually.
6.42
6.42.1
6.42.2
6.42.3
Protection and Automation Functions
6.42 Circuit-Breaker Restrike Protection
SIPROTEC 5, Overcurrent Protection, Manual 853
C53000-G5040-C017-8, Edition 07.2017

Table of Contents