Addr. Parameter C Setting Options Default Setting
_:8101:114 Definite-T 1:Directional
mode
•
non-directional
•
forward
•
reverse
forward
_:8101:111 Definite-T 1:Stabiliz. w.
phase current
0 % to 30 % 10 %
_:8101:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8101:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
_:8101:116 Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
_:8101:130 Definite-T 1:Blocking by
prot. pickup
•
every pickup
•
1-phase pickup
•
multi-phase pickup
•
no pickup
every pickup
_:8101:129 Definite-T 1:Op.mode at
1p dead time
•
blocked
•
non-directional
blocked
_:8101:112 Definite-T 1:Hold mode
1p dead time
0.000 s to 60.000 s 0.040 s
_:8101:140 Definite-T 1:Blocking by Setting options depend on
configuration
Information List
No.
Information Data Class
(Type)
Type
General
_:2311:500 General:>Test of direction SPS I
_:2311:300 General:Test direction ACD O
Group indicat.
_:4501:55 Group indicat.:Pickup ACD O
_:4501:57 Group indicat.:Operate ACT O
Definite-T 1
_:8101:81 Definite-T 1:>Block stage SPS I
_:8101:54 Definite-T 1:Inactive SPS O
_:8101:52 Definite-T 1:Behavior ENS O
_:8101:53 Definite-T 1:Health ENS O
_:8101:60 Definite-T 1:Inrush blocks operate ACT O
_:8101:302 Definite-T 1:Prot.PU blocks operate SPS O
_:8101:301 Definite-T 1:Mode1p dead-tm.active SPS O
_:8101:55 Definite-T 1:Pickup ACD O
_:8101:56 Definite-T 1:Operate delay expired ACT O
_:8101:57 Definite-T 1:Operate ACT O
6.18.7
Protection and Automation Functions
6.18 Directional Negative-Sequence Protection
650 SIPROTEC 5, Overcurrent Protection, Manual