Parameter: Threshold
Default setting (_:101) Threshold = 5.000 V
With the parameter Threshold , you set the threshold value for the measurand which, when exceeded,
generates the output indication
Jump
.
Parameter: Minimum pulse length
Default setting (_:102) Minimum pulse length = 0.10 s
With the parameter Minimum pulse length , you specify a consistent minimum size for the output indica-
tion
Pulse
.
Settings
Addr. Parameter C Setting Options Default Setting
V-jump det. #
_:1 V-jump det. #:Mode
off
on
test
off
_:9 V-jump det. #:Measured
value
phase-to-ground
phase-to-phase
zero-sequence voltage
phase-to-ground
_:101 V-jump det. #:Threshold 0.300 V to 340.000 V 5.000 V
_:102 V-jump det. #:Minimum
pulse length
0.01 s to 60.00 s 0.10 s
Information List
No.
Information Data Class
(Type)
Type
V-jump det. #
_:81 V-jump det. #:>Block stage SPS I
_:501 V-jump det. #:>Pulse extension SPS I
_:54 V-jump det. #:Inactive SPS O
_:52 V-jump det. #:Behavior ENS O
_:53 V-jump det. #:Health ENS O
_:301 V-jump det. #:Jump ACT O
_:302 V-jump det. #:Jump VAB SPS O
_:303 V-jump det. #:Jump VBC SPS O
_:304 V-jump det. #:Jump VCA SPS O
_:305 V-jump det. #:Pulse ACT O
_:306 V-jump det. #:Pulse VAB SPS O
_:307 V-jump det. #:Pulse VBC SPS O
_:308 V-jump det. #:Pulse VCA SPS O
6.50.5
6.50.6
Protection and Automation Functions
6.50 Voltage-Jump Detection
962 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017