Undervoltage Protection with Positive-Sequence Voltage
Setting Values
Threshold value 0.300 V to 200.000 V Increments of 0.001 V
Time delay 0.00 s to 60.00 s Increments of 0.01 s
Dropout ratio 1.01 to 1.20 Increments of 0.01
Current-flow criterion On
Off
Threshold value I> 1 A @ 50 and 100 Irated 0.030 A to 10.000 A Increments of 0.001 A
5 A @ 50 and 100 Irated 0.15 A to 50.00 A Increments of 0.01 A
1 A @ 1.6 Irated 0.001 A to 1.600 A Increments of 0.001 A
5 A @ 1.6 Irated 0.005 A to 8.000 A Increments of 0.001 A
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential 150 mV sec.
Times
Operate time
Approx. 25 ms + OOT
130
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Dropout time Approx. 20 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Inactive, maintained;
Dropout of the pickup induced by blocking or by
increasing the measurand beyond the dropout
threshold
Tolerances
Voltages
0.5 % of the setting value or 0.05 V
Currents 1 % of the setting value or 5 mA (I
rated
= 1 A) or
25 mA (I
rated
= 5 A, f
rated
± 10 %),
valid for protection-class current transformers
1 % of the setting value or 0.1 mA (I
rated
= 1.6 A) or
0.5 mA (I
rated
= 8 A, f
rated
± 10 %),
valid for instrument transformers
Time delays 1 % of the setting value or 10 ms
12.37
130
OOT (Output Operating Time): additional delay of the output medium used, see Chapter 12.1.4 Relay Outputs
Technical Data
12.37 Undervoltage Protection with Positive-Sequence Voltage
SIPROTEC 5, Overcurrent Protection, Manual 1521
C53000-G5040-C017-8, Edition 07.2017