EasyManua.ls Logo

Siemens 7SJ82 - Stage Description

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Stage Description
Logic of a Stage
[louxovpr-211212-01.tif, 1, en_US]
Figure 6-193
Logic Diagram of a Stage: Overvoltage Protection with Any Voltage
i
i
NOTE
If the function Overvoltage protection with any voltage is used in a 1-phase function group, the param-
eter Measured value is not visible.
Method of Measurement
The Method of measurement parameter allows you to define whether the function works with the funda-
mental component or the calculated RMS value.
Measurement of the fundamental comp.:
This method of measurement processes the sampled voltage values and filters out the fundamental
component numerically.
Measurement of the parameter value RMS value:
This method of measurement determines the voltage amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.
Measured Value
The parameter Measured value allows you to select whether the stage uses a measured (directly
connected) voltage or a calculated phase-to-phase voltage.
If the function Overvoltage protection with any voltage is used in a 1-phase function group, the parameter
Measured value is not visible.
6.27.3
Protection and Automation Functions
6.27 Overvoltage Protection with Any Voltage
722 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals