EasyManua.ls Logo

Siemens 7SJ82 - Information List

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[loaweext-140212-01.tif, 1, en_US]
Figure 6-319
Connection of an External Automatic Reclosing Function
There are no setting parameters for operation with external automatic reclosing functions. The function
provides exclusively the following described binary inputs. The external reclosing device can thus have an
influence on the effects of the internal protection functions.
The following connection possibilities exist:
From the external reclosing function, the signal
>Release stages
can be coupled so that the protec-
tion functions use special stages or zones for release. An example is the release of an overreaching zone
with a distance protection or the non-delayed tripping of an overcurrent protection stage in the 1st
reclosing cycle.
For applications with 1-pole tripping, the external reclosing can provide the signal
>1-pole trip
permitted
, based on which the protection functions can switch off the 1-pole circuit breaker.
For applications with reclosing functions only with 1-pole faults and stage or zone releases through the
reclosing function can the signal
>1-pole AR only
be connected. The protection functions use this
information to allow the stage or zone release only affect 1-pole faults.
Information List
No.
Information Data Class
(Type)
Type
Ext
_:6661:51 Ext:Mode (controllable) C
_:6661:501 Ext:>Release stages I
_:6661:502 Ext:>1-pole trip permitted I
_:6661:503 Ext:>1-pole AR only I
_:6661:52 Ext:Behavior O
_:6661:53 Ext:Health O
_:6661:54 Ext:Inactive O
6.45.6.2
Protection and Automation Functions
6.45 Automatic Reclosing Function
SIPROTEC 5, Overcurrent Protection, Manual 923
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals