Figure 3-69
Diagnostic Data of the Protection-Interface Log - HDLC (Log - Layer)
Table 3-19 Description of Diagnostic Data of the Protection-Interface Log - HDLC (Log - Layer)
Protection Interfaces - Log
Type
Name Values Description - HDLC Link
Layer Diagnostic Informa-
tion (in Direction of
Outside Interface)
HDLC RXHPFramesOK Number of corresponding
frames (16 bit counter)
Incoming telegrams, high
priority, OK
HDLC RXLPFramesOK Number of corresponding
frames (16 bit counter)
Incoming telegrams, low
priority, OK
HDLC RXHPFramesERR Number of corresponding
frames (16 bit counter)
Incoming telegrams, high
priority, faulty
HDLC RXLPFramesERR Number of corresponding
frames (16 bit counter)
Incoming telegrams, low
priority, faulty
HDLC TXHPFramesOK Number of corresponding
frames (16 bit counter)
Sending telegrams, high
priority, OK
HDLC TXLPFramesOK Number of corresponding
frames (16 bit counter)
Sending telegrams, low
priority, OK
System Functions
3.5 Protection Communication
140 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017