Priority 2:
Response time, total approx.
For 2 ends Minimum 9 ms
Typical 16 ms
For 3 ends Minimum 12 ms
Typical 18 ms
For 6 ends Minimum 17 ms
Typical 23 ms
Dropout times, total approx.
For 2 ends Typical 24 ms
For 3 ends Typical 25 ms
For 6 ends Typical 32 ms
Priority 3
51
Response time, total approx.
For 2 ends Minimum
Typical 100 ms
For 3 ends Minimum
Typical 150 ms
For 6 ends Minimum
Typical 200 ms
Dropout times, total approx.
For 2 ends Typical 100 ms
For 3 ends Typical 150 ms
For 6 ends Typical 200 ms
51
Times cannot be determined because the signals are transmitted in fragments.
Technical Data
12.2 Protection Interface and Protection Topology
1418 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017