Up to 50th harmonic, f
rated
= 50 Hz 3 % of setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
Up to 50th harmonic, f
rated
= 60 Hz 4 % of setting value or 20 mA (I
rated
= 1 A)
or 100 mA (I
rated
= 5 A), (f
rated
± 10 %)
Time delays 1 % of the setting value or 10 ms
Technical Data
12.19 Undercurrent Protection
SIPROTEC 5, Overcurrent Protection, Manual 1487
C53000-G5040-C017-8, Edition 07.2017