EasyManua.ls Logo

Siemens 7SJ82 - Page 1568

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range f
rated
- 0.20 Hz < f
rated
+ 0.20 Hz
Tolerance ± 5 mHz in the V
rated
range
Range f
rated
- 3.00 Hz < f
rated
+ 3.00 Hz
Tolerance ± 10 mHz in the V
rated
range
Frequency range (expanded) 25 Hz to 80 Hz; operational measured values
10 Hz to 80 Hz; functional measured values, system
frequency
Tolerance 20 mHz in the range f
rated
± 10 % for rated values
Statistical Values of the Device
Device operating hours h
Range 0 to 9 999 999 h
Tolerance 1 h
Statistical Values of the Circuit Breaker
Op.cnt. (operation counter)
Range 0 to 999 999 999
Tolerance None
∑I Off (sum of the primary currents switched off) A, kA, MA, GA, TA, PA primary
Range 0 to 9.2 e+15
Operating hours h
Range 0 to 9 999 999 h
Tolerance 1 h
Circuit breaker open hours h
Range 0 to 9 999 999 h
Tolerance 1 h
Statistical Values of the Disconnector
Op.cnt.
(operation counter)
Range 0 to 999 999 999
Tolerance None
Technical Data
12.70 Operational Measured Values and Statistical Values
1568 SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017

Table of Contents