Figure 3-94 Setting Sheet: Transformer Data
In the function group Voltage/current 3-phase, you set the rated current and the rated voltage (see following
figure). Rated current, rated voltage are the reference variables for the percent setting.
[scui3phd, 1, en_US]
Figure 3-95 Reference Data for Percentage Settings
The following figure shows the threshold value of the Overcurrent protection function in the primary view at
1500 A.
System Functions
3.9 General Notes for Setting the Threshold Value of Protection Functions
SIPROTEC 5, Overcurrent Protection, Manual 173
C53000-G5040-C017-8, Edition 07.2017