ANSI Function Abbr.
Available in 7SJ82
Available in 7SJ85
Template 1
Template 2
Template 3
Template 4
Template 5
Template 6
Template 7
47 Overvoltage protection, negative-
sequence system
V2> x x
47 Overvoltage protection with negative-
sequence voltage/positive-sequence
voltage
V2/V1> x x
59N Overvoltage protection, zero-sequence
system
V0> x x
59 Overvoltage protection, 3-phase or 1-
phase, universal, Vx
Vx> x x
59C Peak overvoltage protection for capaci-
tors
x x x 2 x
60 Voltage-comparison supervision x x
60C Current unbalance protection for
capacitors, 3-phase
Iunbal> x x x 2 x
60C Current unbalance protection for
capacitors, 1-phase
Iunbal> x x
67 Directional overcurrent protection,
phases – advanced
I>, ∠(V,I) x x
67 Directional overcurrent protection,
phases – basic
I>, ∠(V,I) x x x x
67N Directional overcurrent protection,
ground - advanced
IN>, ∠
(V,I)
x x
67N Directional overcurrent protection,
ground - basic
IN>, ∠
(V,I)
x x x
67Ns Directional sensitive ground-fault
detection for systems with resonant or
isolated neutral
INs>, ∠
(V,I)
x x x
67Ns Directional sensitive ground-fault
detection via admittance measurement
for systems with resonant or isolated
neutral
G0>, B0> x x
67Ns Transient ground-fault function, for
transient and permanent ground faults
in resonant-grounded or isolated
networks
W0p,tr> x x
67Ns Sensitive ground-fault detection for
systems with resonant or isolated
neutral with phasor measurement of
3rd or 5th harmonic
V0>, ∠
(Uharm.,I
harm.)
x x
67Ns Sensitive ground-fault detection for
systems with resonant or isolated
neutral via 3I0 pulse pattern detection
IN-pulse x x
74TC Trip-circuit supervision TCS x x
79 Automatic reclosing AREC x x
81O Overfrequency protection f> x x
81U Underfrequency protection f< x x
81U Underfrequency load shedding x x
Applications
4.2 Application Templates and Functional Scope for the Devices 7SJ82/7SJ85
SIPROTEC 5, Overcurrent Protection, Manual 191
C53000-G5040-C017-8, Edition 07.2017

Table of Contents