Addr. Parameter C Setting Options Default Setting
_:15 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:103 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: AR cycle 3
_:31 User curve #:Effected by
AR cycle 3
no
yes
no
_:38 User curve #:Stage
blocked
no
yes
no
_:16 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:104 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: AR cycle>3
_:32 User curve #:Effected by
AR cycle gr. 3
no
yes
no
_:39 User curve #:Stage
blocked
no
yes
no
_:17 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:105 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.s: Cold load PU
_:33 User curve #:Effect. b.
cold-load pickup
no
yes
no
_:40 User curve #:Stage
blocked
no
yes
no
_:18 User curve #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.15 A to 175.00 A 7.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:106 User curve #:Time dial 0.05 to 15.00 1.00
Dyn.set: bin.input
_:34 User curve #:Effected by
binary input
no
yes
no
_:41 User curve #:Stage
blocked
no
yes
no
Protection and Automation Functions