EasyManua.ls Logo

Siemens 7SJ82 - Page 581

Siemens 7SJ82
1638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The following mechanisms are applied:
For reporting the direction result, the fundamental-component value of the zero-sequence voltage must
exceed the V0> threshold value in a time slot of 100 ms after the ground-fault ignition. This effec-
tively suppresses wrong indications as a result of switching operations.
The fundamental-component value of the zero-sequence voltage V0 is not influenced by switching oper-
ations and is thus a good criterion for distinguishing the ground fault from a switching procedure. The
condition that the fundamental-component value must exceed the V0> threshold value for
reporting the direction result effectively suppresses the influence of switching operations.
For rare cases in which high zero-sequence voltages occur over longer time ranges after switching off the
feeder or line, a criterion based on the positive-sequence current is also effective. This criterion compares
the positive-sequence current before and after the transient event and thus detects a disconnection. In
case of disconnection, the direction result is not reported.
Through stabilization mechanisms, the direction result is reported 100 ms after the ground-fault ignition.
Thus a pickup occurs with a 100-ms delay.
If the stage is used in a 1-phase function group, the additional criterion via the positive-sequence current
is not effective.
The function detects transient occurrences in the zero-sequence voltage. In systems with operational
zero-sequence voltages, if the measuring voltage is switched on, the function can internally be started. If
the fundamental-component value of the zero-sequence voltage does not exceed the threshold of the
Maximum operational V0 parameter in a time slot of 100 ms after the function start, the function is
reset internally.
Trip Logic
[loauswis-240113-01.tif, 3, en_US]
Figure 6-132
Trip Logic Diagram
Protection and Automation Functions
6.15 Sensitive Ground-Fault Detection
SIPROTEC 5, Overcurrent Protection, Manual 581
C53000-G5040-C017-8, Edition 07.2017

Table of Contents

Related product manuals